Product Highlights
Temperatures up to 500oF (260oC)
Power remains constant regardless of temperature
Can be cut-to-length at job site
Ideal for a wide range of general purpose applications in corrosive environments:
- Freeze protection
- Viscosity control
- High temperature process control
- Asphalt plants
- Oil refineries
- Mines
- Chemical and petrochemical processing areas
- Other explosive and corrosive atmospheres
- Severe arctic cold
Specifications
- Maximum exposure temperature is 500oF (260oC)
- Moisture, chemical, flame, and radiation resistant
- 12AWG bus wires
- Dimensions 0.2" x 0.3" (5 x 8mm)
- 41 lb. (19kg) per 500-foot (152m) spool
TEFLON® is a registered Trademark of DuPont used under license.
Approvals
Ordinary Locations Hazardous Location (T3 rated): Class I Division 2 Groups B, C, D Class II Division 2 Groups F, G Class III Division 2
 
Approval valid only when used with appropriate heating cable and installation accessories, and installed in accordance with all applicable instructions, codes, and regulations.
Maximum Circuit Length in ft (m)
| Cable |
120VAC |
208VAC |
240VAC |
277VAC |
480VAC |
4 watts / ft (13 watts / m) |
310 (95) |
537 (164) |
620 (189) |
716 (218) |
1240 (378) |
8 watts / ft (26 watts / m) |
220 (67) |
381 (116) |
440 (134) |
508 (155) |
880 (268) |
12 watts / ft (39 watts / m) |
180 (55) |
312 (95) |
360 (110) |
416 (127) |
720 (220) |
Circuit Module Length in ft (m)
| Cable |
120VAC |
208VAC |
240VAC |
277VAC |
480VAC |
4 watts / ft (13 watts / m) |
4.0 (1.2) |
4.0 (1.2) |
4.0 (1.2) |
4.0 (1.2) |
8.0 (2.4) |
8 watts / ft (26 watts / m) |
4.0 (1.2) |
4.0 (1.2) |
4.0 (1.2) |
4.0 (1.2) |
6.0 (1.8) |
12 watts / ft (39 watts / m) |
2.0 (0.6) |
6.0 (1.8) |
4.0 (1.2) |
4.0 (1.2) |
6.0 (1.8) |
Note: when ordering, please allow a minimum of 1 module length extra for terminations. |